Compact size controller that can be mounted on a small panel space
| 원산지 | JAPAN |
|---|---|
| 제조사 | RKC |
| 브랜드 | RKC |
| 무게 | 1kg |
Main features
- 48(W)×24(H)mm sized compact temperature controller
![]() | Compact size controller that can be mounted on a small panel space Large easy-to-read PV display on a compact front panel |
- Control state discriminating type self-tuning
![]() |
PID parameters are automatically tuned when control is determined to be disturbed Autotuning function is also available. |
- Communication function (RS-485) is available (Optional)
![]() | Up to 31 controllers can be multidrop connected over the RS-485 communication line. Communication protocol can be selected from RKC standard or MODBUS protocol. |
- Analog Retransmission Output function is available (Optional)
![]() | The output 1 can be configured as an analog retransmission output. The output 1 can be configured as an analog retransmission output. With this function, the measured value can be retransmitted as an analog current signal (4-20mA /0-20mA). |
Two types of colors; black base or white base
![]() | Two types of colors are offered to match the machine. |
Main specification
- Number of Inputs :1 point
- Input type : *See the Input Range Code for the input range.
1)Thermocouple : K, J, T, S, R, E, B, N, W5Re/W26Re, U, L, PLII
2)RTD: Pt100 or JPt100
3)DC voltage: 0 to 5V dc, 1 to 5V dc
4)DC current: 0 to 20mA dc, 4 to 20mA dc * A 250Ω external resistor is required.
- Sampling time: 0.5 sec. 0.25sec (Selectable)
- Input Digital Filter:1 to 100 sec (OFF when 0 is set.)
- Measurement accuracy:±(0.3% of displayed value+1 digit) *Depends on the input and the range.
- Outputs (OUT1)
1) Relay contact output : 1a contact
2) Voltage pulse output for SSR driving: 0/12V dc
3) DC Current output : 0 to 20mA, 4 to 20mA dc
- Output 2 (OUT2)
1) Relay contact output : 1a contact
2) Voltage pulse output for SSR driving: 0/12V dc
- Alarm outputs (max.2 points): Temperature alarm, Control loop break alarm
- External contact input (max. 2 points): RUN/STOP, SV1/SV2, Alarm interlock release switching
- Analog Retransmission Output:PV, DEV, SV, MV * Selectable
- Communication Function: Communication method RS-485
- Supply voltage (Rating): 100 to 240Vac/ 24Vac/ 24Vdc
- Ambient temperature: -10 to +55°C
- Weight: Approx.110g
- Safety standards:
- UL: UL61010-1
- cUL: CAN/CSA-22.2 NO.61010-1
- CE Marking:
LVD: EN61010-1
EMC: EN61326-1
RoHS: EN IEC 63000
- RCM: EN55011
- UKCA marking:
Electrical Safety: EN61010-1
EMC: EN61326-1
RoHS: EN IEC 63000
External dimensions